Communication cables - Specifications for test methods - Part 1-9: Electrical test methods - Unbalance attenuation (transverse conversion loss TCL transverse conversion transfer loss TCTL)

This draft European Standard details the test methods to determine the attenuation of converted differential-mode signals into common-mode signals, and vice versa, due to balance characteristics of cables used in analogue and digital communication systems by using the transmission measurement method. The unbalance attenuation is measured in, respectively converted to, standard operational conditions. If not otherwise specified, e.g. by product specifications, the standard operational conditions are a differential-mode which is matched with its nominal characteristic impedance (e.g. 100 Ω) and a common-mode which is loaded with 50 Ω. The difference between the (image) unbalance attenuation (matched conditions in the differential and common-mode) to the Betriebs- (operational) unbalance attenuation (matched conditions in differential-mode and 50 Ω reference load in the common-mode) is small provided the common-mode impedance Zcom is in the range of 25 Ω to 75 Ω.
For cables having a nominal impedance of 100 Ω, the value of the common-mode impedance Zcom is about 75 Ω for up to 25 pair- count unscreened pair cables, 50 Ω for common screened pair cables and more than 25 pair- count unscreened pair cables, and 25 Ω for individually screened pair cables. The impedance of the common-mode circuit Zcom can be measured more precisely either with a time domain reflectometer (TDR) or a network analyser. The two conductors of the pair are connected together at both ends and the impedance is measured between these conductors and the return path.
This draft European Standard is bound to be read in conjunction with prEN 50289-1-1, which contains essential provisions for its application.

Kommunikationskabel - Spezifikationen für Prüfverfahren Teil 1-9: Elektrische Prüfverfahren - Unsymmetriedämpfung (Unsymmetriedämpfung am nahen und am fernen Ende)

Diese Europäische Norm beschreibt die Prüfverfahren zur Bestimmung der Dämpfung wegen der symmetrischen Eigenschaften der in analogen und digitalen Kommunikationssystemen verwendeten Kabel umgewandelter Gegentaktsignale in Gleichtaktsignale und umgekehrt mit Hilfe des Messverfahrens des Übertragungsverhaltens. Die Unsymmetriedämpfung wird bei Standardbetriebsbedingungen gemessen bzw. in diese umgewandelt. Wenn nicht anders festgelegt, z. B. durch Produktspezifikationen, sind die Standard-betriebsbedingungen der Gegentaktbetrieb, der mit seinem Nennwellenwiderstand (z. B. 100 Ω) angepasst ist, und der Gleichtaktbetrieb, der mit 50 Ω abgeschlossen ist. Die Differenz zwischen der (Spiegel-) Unsymmetriedämpfung (angepasste Bedingungen im Gegentakt- und im Gleichtaktbetrieb) und der (Betriebs-)Unsymmetriedämpfung (angepasste Bedingungen im Gegentaktbetrieb und 50 Ω Referenzlast im Gleichtaktbetrieb) ist klein, vorausgesetzt, die Gleichtaktimpedanz Zcom liegt im Bereich von 25 Ω bis 75 Ω.
Für Kabel mit einer Nennimpedanz von 100 Ω beträgt der Wert der Gleichtaktimpedanz Zcom etwa 75 Ω für bis zu 25-paarige ungeschirmte Zweidrahtleitungen, 50 Ω für gemeinsam abgeschirmte Zweidrahtleitungen und mehr als 25-paarige ungeschirmte Zweidrahtleitungen und 25 Ω für einzeln abgeschirmte Zweidraht-leitungen. Die Impedanz der Gleichtaktschaltung Zcom kann mit einem Zeitbereichsreflektometer (en: time domain reflectometer, TDR) oder mit einem Netzwerkanalysator genauer gemessen werden. Die beiden Leiter des Paares werden an beiden Enden miteinander verbunden und es wird die Impedanz zwischen diesen Leitern und dem Rückweg gemessen.
Diese Europäische Norm ist in Verbindung mit EN 50289-1-1 zu lesen, die grundlegende Festlegungen zur Anwendung dieser Norm enthält.

Câbles de communication - Spécifications des méthodes d'essai Partie 1-9: Méthodes d'essais électriques - Affaiblissement de disymétrie (perte de conversion longitudinale, perte de transfert de conversion longitudinale)

Komunikacijski kabli - Specifikacije za preskusne metode - 1-9. del: Električne preskusne metode - Neenakomerno slabljenje (prečna izguba pretvorbe TCL, prečna izguba pretvorbe prenosa TCTL)

Ta osnutek evropskega standarda podrobno navaja preskusne metode za določanje slabljenja diferencialnih signalov, ki so pretvorjeni v skupne signale, in obratno zaradi ravnovesnih značilnosti kablov, ki se uporabljajo v analognih in digitalnih komunikacijskih sistemih, z metodo merjenja prenosa. Neenakomerno slabljenje se meri v običajnih pogojih delovanja po pretvorbi. Če ni določeno drugače, npr. v specifikacijah izdelka, so običajni pogoji delovanja diferencialni način, ki se ujema z nazivno značilno impedanco (npr. 100 Ω) in skupnim načinom z obremenitvijo 50 Ω. Razlika med (slikovnim) neenakomernim dušenjem (enaki pogoji v diferencialnem in skupnem načinu) in (operativnim) neenakomernim dušenjem Betriebs (enaki pogoji v diferencialnem načinu in 50-Ω referenčna obremenitev v skupnem načinu) je majhna, če je impedanca Zcom skupnega načina v razponu med 25 Ω in 75 Ω.
Za kable z nazivno impedanco 100 Ω je vrednost impedance Zcom skupnega načina približno 75 Ω za neoklopljene kable z do 25 pari, 50 Ω za običajne oklopljene parne kable in neoklopljene parne kable z več kot 25 pari ter 25 Ω za posamezno oklopljene parne kable. Impedanca Zcom skupnega vezja se lahko natančneje izmeri z reflektometrom (TDR) ali analizatorjem omrežja. Prevodnika para sta povezana na obeh koncih, impedanca pa se meri med tema prevodnikoma in povratno potjo.
Ta osnutek evropskega standarda je treba brati v povezavi s standardom prEN 50289-1-1, ki vključuje bistvene določbe za njegovo uporabo.

General Information

Status
Published
Public Enquiry End Date
19-Oct-2016
Publication Date
30-Mar-2017
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
22-Mar-2017
Due Date
27-May-2017
Completion Date
31-Mar-2017

Relations

Buy Standard

Standard
EN 50289-1-9:2017 - BARVE
English language
21 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Draft
prEN 50289-1-9:2016 - BARVE
English language
21 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 50289-1-9:2017
01-maj-2017
1DGRPHãþD
SIST EN 50289-1-9:2002
.RPXQLNDFLMVNLNDEOL6SHFLILNDFLMH]DSUHVNXVQHPHWRGHGHO(OHNWULþQH
SUHVNXVQHPHWRGH1HHQDNRPHUQRVODEOMHQMH SUHþQDL]JXEDSUHWYRUEH7&/
SUHþQDL]JXEDSUHWYRUEHSUHQRVD7&7/
Communication cables - Specifications for test methods - Part 1-9: Electrical test
methods - Unbalance attenuation (transverse conversion loss TCL transverse conversion
transfer loss TCTL)
Kommunikationskabel - Spezifikationen für Prüfverfahren Teil 1-9: Elektrische
Prüfverfahren - Unsymmetriedämpfung (Unsymmetriedämpfung am nahen und am
fernen Ende)
Câbles de communication - Spécifications des méthodes d'essai Partie 1-9: Méthodes
d'essais électriques - Affaiblissement de disymétrie (perte de conversion longitudinale,
perte de transfert de conversion longitudinale)
Ta slovenski standard je istoveten z: EN 50289-1-9:2017
ICS:
33.120.20 äLFHLQVLPHWULþQLNDEOL Wires and symmetrical
cables
SIST EN 50289-1-9:2017 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 50289-1-9:2017

---------------------- Page: 2 ----------------------

SIST EN 50289-1-9:2017


EUROPEAN STANDARD
EN 50289-1-9

NORME EUROPÉENNE

EUROPÄISCHE NORM
March 2017
ICS 33.120.20 Supersedes EN 50289-1-9:2001
English Version
Communication cables - Specifications for test methods -
Part 1-9: Electrical test methods - Unbalance attenuation
(transverse conversion loss TCL transverse conversion transfer
loss TCTL)
Câbles de communication - Spécifications des méthodes Kommunikationskabel - Spezifikationen für Prüfverfahren
d'essai Partie 1-9: Méthodes d'essais électriques - Teil 1-9: Elektrische Prüfverfahren - Unsymmetriedämpfung
Affaiblissement de disymétrie (perte de conversion (Unsymmetriedämpfung am nahen und am fernen Ende)
longitudinale, perte de transfert de conversion
longitudinale)
This European Standard was approved by CENELEC on 2016-12-16. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any
alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden,
Switzerland, Turkey and the United Kingdom.


European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2017 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
 Ref. No. EN 50289-1-9:2017 E

---------------------- Page: 3 ----------------------

SIST EN 50289-1-9:2017
EN 50289-1-9:2017 (E)
Contents Page
European foreword . 3
1 Scope. 4
2 Normative references . 4
3 Terms and definitions . 4
4 Test method . 5
4.1 Method A: measurement using balun setup . 5
4.1.1 Test equipment . 5
4.1.2 Test sample . 5
4.1.3 Calibration procedure . 6
4.1.4 Measuring procedure . 8
4.1.5 Expression of test results . 10
4.2 Method B: measurement using balun-less setup . 11
4.2.1 Test equipment . 11
4.2.2 Test sample . 11
4.2.3 Calibration procedure . 12
4.2.4 Measuring procedure . 12
4.2.5 Expression of test results . 13
5 Test report . 14
Annex A (informative) General background of unbalance attenuation . 15
A.1 General . 15
A.2 Unbalance attenuation near end and far end . 16
A.3 Theoretical background . 17
Bibliography . 21

2

---------------------- Page: 4 ----------------------

SIST EN 50289-1-9:2017
EN 50289-1-9:2017 (E)
European foreword
This document [EN 50289-1-9:2017] has been prepared by CLC/TC 46X “Communication cables”.
The following dates are fixed:
• latest date by which this document has to be implemented (dop) 2017-09-16
at national level by publication of an identical national
standard or by endorsement
• latest date by which the national standards conflicting with (dow) 2019-12-16
this document have to be withdrawn
This document supersedes EN 50289-1-9:2001.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
EN 50289-1, Communication cables — Specifications for test methods, is currently composed with the
following parts:
— Part 1-1: Electrical test methods — General requirements;
— Part 1-2: Electrical test methods — DC resistance;
— Part 1-3: Electrical test methods — Dielectric strength;
— Part 1-4: Electrical test methods — Insulation resistance;
— Part 1-5: Electrical test methods — Capacitance;
— Part 1-6: Electrical test methods — Electromagnetic performance;
— Part 1-7: Electrical test methods — Velocity of propagation;
— Part 1-8: Electrical test methods — Attenuation;
— Part 1-9: Electrical test methods — Unbalance attenuation (transverse conversion loss TCL transverse
conversion transfer loss TCTL);
— Part 1-10: Electrical test methods — Crosstalk;
— Part 1-11: Electrical test methods — Characteristic impedance, input impedance, return loss;
— Part 1-12: Electrical test methods — Inductance;
— Part 1-13: Electrical test methods — Coupling attenuation or screening attenuation of patch cords /
coaxial cable assemblies / pre-connectorised cables;
— Part 1-14: Electrical test methods — Coupling attenuation or screening attenuation of connecting
hardware;
— Part 1-15: Electromagnetic performance — Coupling attenuation of links and channels (Laboratory
conditions);
— Part 1-16: Electromagnetic performance — Coupling attenuation of cable assemblies (Field conditions);
— Part 1-17: Electrical test methods — Exogenous Crosstalk ExNEXT and ExFEXT.
3

---------------------- Page: 5 ----------------------

SIST EN 50289-1-9:2017
EN 50289-1-9:2017 (E)
1 Scope
This European Standard details the test methods to determine the attenuation of converted differential-mode
signals into common-mode signals, and vice versa, due to balance characteristics of cables used in analogue
and digital communication systems by using the transmission measurement method. The unbalance
attenuation is measured in, respectively converted to, standard operational conditions. If not otherwise
specified, e.g. by product specifications, the standard operational conditions are a differential-mode which is
matched with its nominal characteristic impedance (e.g. 100 Ω) and a common-mode which is loaded with
50 Ω. The difference between the (image) unbalance attenuation (matched conditions in the differential and
common-mode) to the operational (Betriebs) unbalance attenuation (matched conditions in differential-mode
and 50 Ω reference load in the common-mode) is small provided the common-mode impedance Z is in
com
the range of 25 Ω to 75 Ω.
For cables having a nominal impedance of 100 Ω, the value of the common-mode impedance Z is about
com
75 Ω for up to 25 pair- count unscreened pair cables, 50 Ω for common screened pair cables and more than
25 pair- count unscreened pair cables, and 25 Ω for individually screened pair cables. The impedance of the
common-mode circuit Z can be measured more precisely either with a time domain reflectometer (TDR)
com
or a network analyser. The two conductors of the pair are connected together at both ends and the
impedance is measured between these conductors and the return path.
This European Standard is bound to be read in conjunction with EN 50289-1-1, which contains essential
provisions for its application.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 50289-1-1:2017, Communication cables — Specifications for test methods — Part 1-1: Electrical test
methods — General requirements
EN 50289-1-8, Communication cables - Specifications for test methods - Part 1-8: Electrical test methods -
Attenuation
EN 50290-1-2, Communication cables - Part 1-2: Definitions
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 50290-1-2 and the following apply.
3.1
unbalance attenuation
logarithmic ratio of the differential-mode power (transmission signal of a balanced pair) to the common-mode
power (signal in the pair to ground/earth unbalanced circuit) measured at the near and at the far end
Note 1 to entry: The (operational) unbalance attenuation is described by the logarithmic ratio of the differential-mode
power to the common-mode power in standard operational conditions. If not otherwise specified, e.g. by product
specifications, the standard operational conditions are a differential-mode which is matched with its nominal
characteristic impedance (e.g. 100 Ω) and a common-mode which is loaded with 50 Ω.
 
PZU
diff diff com
 
a= 10×lg = 20×lg +×10 lg (1)
u
 
PZU
com com  diff 
where
Pdiff is the power in the differential-mode (balanced) circuit;
4

---------------------- Page: 6 ----------------------

SIST EN 50289-1-9:2017
EN 50289-1-9:2017 (E)
Pcom is the power in the common-mode (unbalanced) circuit;
U is the voltage in the differential-mode (balanced) circuit;
diff
Ucom is the voltage in the common-mode (unbalanced) circuit;
Z is the characteristic impedance of the differential-mode (balanced) circuit;
diff
Zcom is the characteristic impedance of the common-mode (unbalanced) circuit.
3.2
transverse conversion loss
TCL
logarithmic ratio of the differential-mode injected signal at the near end to the resultant common-mode signal
at the near end of a balanced pair, and which is equal to unbalance attenuation at near end when the CUT is
terminated with the same impedances as defined for unbalance attenuation measurement
Note 1 to entry: This definition stems from ITU-G.117.
3.3
transverse conversion transfer loss
TCTL
logarithmic ratio of the differential-mode injected signal at the near end to the resultant common-mode signal
at the far end of a balanced pair, and which is equal to unbalance attenuation at far end when the CUT is
terminated with the same impedances as defined for unbalance attenuation measurement
Note 1 to entry: This definition stems from ITU-G.117.
4 Test method
4.1 Method A: measurement using balun setup
4.1.1 Test equipment
a) It is mandatory to create a defined return (common-mode) path. This is achieved by grounding all other
pairs and screen(s) if present in common to the balun ground. However in addition in the case of
unscreened cables the cable under test shall be wound onto a grounded metal drum. The drum surface
may have a suitable groove, wide enough to contain the cable, and shall be adequate to hold 100 m of
cable in one layer. The pair under test shall be terminated with differential-mode and common-mode
terminations and grounded at near and far ends
b) A network analyser or generator/receiver combination suitable for the required frequency and dynamic
range.
c) The baluns shall have a common-mode port and the characteristics given in EN 50289-1-1:2017,
Table 1.
d) Time domain reflectometer (optional).
4.1.2 Test sample
The ends of the cable under test (CUT) shall be prepared so that the twisting of the pairs/quads is maintained
up to the terminals of the test equipment. If not otherwise specified the CUT shall have a length of
100 m ± 1 m. For the measurement or evaluation of the equal level unbalance attenuation at the far end the
following applies: if the CUT length is not otherwise specified and the attenuation of the CUT at the highest
frequency to be measured is higher than or equal to 80 dB the length of the CUT may be reduced to limit the
attenuation to maximum 80 dB.
All pairs not under test and all screens shall be connected in common to the same ground as the balun at
both ends of the CUT.
5

---------------------- Page: 7 ----------------------

SIST EN 50289-1-9:2017
EN 50289-1-9:2017 (E)
For unscreened cables the CUT shall be wound tightly around the metal drum in one layer. The distance
between the windings should be at least the diameter of the cable. The metal drum shall be connected to the
same ground as the balun, e.g. by fixing the baluns to the drum.
4.1.3 Calibration procedure
a) The reference line calibration (0 dB-line) shall be determined by connecting coaxial cables between the
analyser input and output. The same coaxial cables shall also be used for the balun loss and unbalance
attenuation measurements. The calibration shall be established over the whole frequency range
specified in the relevant cable specification. This calibration method is valid for closely matched baluns
that satisfy the characteristics of Table 1.
b) Figure 1 gives the schematic for the measurement of the differential-mode loss of the baluns. Two baluns
are connected back to back on the symmetrical output side and their attenuation measured over the
specified frequency range. The connection between the two baluns shall be made with negligible loss.

Key
U
voltage at network analyser port or signal generator
0
U
voltage at network analyser port or receiver
1
U
voltage at symmetrical port of baluns
diff
Figure 1 — Test set-up for the measurement of the differential-mode loss of the baluns
The differential-mode loss of the baluns is given by:

U
0

α =0,5× 20×lg =−×0,5 20×lg S (2)
( )
diff 21

U
1

where
α is the differential-mode loss of the balun (dB);
diff
S is the scattering parameter S (forward transmission coefficient) where port 1 is the primary
21 21
(unbalanced side) side of the near end balun and port 2 is the primary side (unbalanced
port) of the far end balun.
6

---------------------- Page: 8 ----------------------

SIST EN 50289-1-9:2017
EN 50289-1-9:2017 (E)
c) Figure 2 gives the schematic for the measurement of the common-mode loss of the baluns. The baluns
used in b) are connected together; the unbalanced balun ports are terminated with the nominal test
equipment impedance, the test equipment is connected to the common-mode ports (centre taps) of the
baluns.

Key
U
voltage at network analyser port or signal generator
0
U
voltage at network analyser port or receiver
1
Figure 2 — Test set-up for the measurement of the common-mode loss of the baluns
The common-mode loss of the baluns is given by:
 
U
0
 
α =0,5× 20×lg =−×0,5 20×lg S (3)
( )
com 21
 
U
1
 
where
α is the common-mode loss of the balun (dB);
com
S is the scattering parameter S (forward transmission coefficient) where port 1 is the common-
21 21
mode port of the near end balun and port 2 is the common-mode port of the far end balun.
d) The operational attenuation of the balun α takes into account the common-mode and differential-
balun
mode losses of the balun:
α αα+ (4)
balun diff com
where
α is the operational attenuation or intrinsic loss of the balun (dB).
balun
NOTE More precise results can be obtained using either poling of the baluns for α and α and averaging the
diff com
results or using three baluns. In the latter case, the assumption of identical baluns is not required.
7
=

---------------------- Page: 9 ----------------------

SIST EN 50289-1-9:2017
EN 50289-1-9:2017 (E)
e) The voltage ratio of the balun can be expressed by the turns ratio of the balun and the operational
attenuation of the balun:
U Z
diff diff
20×lg =10×−lg α
balun
U Z
00
(5)
U Z
diff diff
20×lg =10×−lg α
balun
U Z
11
where
Udiff is the differential-mode voltage at the input of the cable under test (V);
U is the voltage at the network analyser port or signal generator (V);
0
Zdiff is the characteristic impedance of the differential-mode circuit (Ω);
Z is the output impedance of the network analyser or signal generator (Ω);
0
U1 is the voltage at the input of the load (V);
Z is the input impedance of the load (Ω).
1
4.1.4 Measuring procedure
All pairs/quads of the cable shall be measured at both ends of the CUT. The unbalance attenuation shall be
measured over the whole-specified frequency range and at the same frequency points as for the calibration
procedure.
The measurement is done under standard operational conditions, i.e. one is measuring the Betriebs-
(operational) unbalance attenuation. If not otherwise specified, e.g. by product specifications, the standard
operational conditions are a differential-mode which is matched with its nominal characteristic impedance
(e.g. 100 Ω) and a common-mode which is loaded with 50 Ω.
Figure 3 gives a schematic of the measurement for unbalance attenuation at the near end.

Figure 3 — Test set-up for unbalance attenuation at near end (TCL)
8

---------------------- Page: 10 ----------------------

SIST EN 50289-1-9:2017
EN 50289-1-9:2017 (E)
U
0
α =20×lg =−×20 lg S (6)
meas 21
U
n, com
where
α is the measured attenuation (dB);
meas
S is the scattering parameter S (forward transmission coefficient) where port 1 is the primary
21 21
(unbalanced) side of the near end balun and port 2 is the common-mode port of the near
end balun
U voltage in the primary (unbalanced) circuit at the near end balun
0
U voltage in the common-mode circuit (V) at the near end balun
n,com
Figure 4 gives a schematic of the measurement for unbalance attenuation at far end.

Figure 4 — Test set-up for unbalance attenuation at far end (TCTL)
U
0
α =20×lg =−×20 lg S (7)
meas 21
U
f , com
where
α is the measured attenuation (dB);
meas
S is the scattering parameter S (forward transmission coefficient) where port 1 is the primary
21 21
(unbalanced) side of the near end balun and port 2 is the common-mode port of the far
end balun;
U voltage in the primary (unbalanced) circuit at the near end balun;
0
U voltage in the common-mode circuit (V) at the far end balun.
n,com
9

---------------------- Page: 11 ----------------------

SIST EN 50289-1-9:2017
EN 50289-1-9:2017 (E)
4.1.5 Expression of test results
The unbalance attenuation is defined as the logarithmic ratio of the differential-mode power to the common-
mode power:
P
UZ
diff
diff com
α = 20×lg = 20×lg +×10 lg (8)
u,n
UZ
P
u,f
diff
n,com
n,com
f,com
f,com
where
α is the unbalance attenuation (dB) at the near end (subscript n) respectively far end (subscript
u
f);
P is the common-mode power (W) at the near end (subscript n) respectively far end (subscript
com
f);
P is the differential-mode power (W);
diff
Z is the nominal characteristic impedance of the differential-mode of the CUT;
diff
Z is the standardized operational impedance of the common-mode, 50 Ω.
com
When measuring with S-parameter test-sets, the output voltage of the generator is measured instead of the
differential-mode voltage in the cable under test. Taking the operational attenuation of the balun into account,
the formula for the unba
...

SLOVENSKI STANDARD
oSIST prEN 50289-1-9:2016
01-oktober-2016
.RPXQLNDFLMVNLNDEOL6SHFLILNDFLMH]DSUHVNXVQHPHWRGHGHO(OHNWULþQH
SUHVNXVQHPHWRGH1HHQDNRPHUQRVODEOMHQMH SUHþQDL]JXEDSUHWYRUEH7&/
SUHþQDL]JXEDSUHWYRUEHSUHQRVD7&7/
Communication cables - Specifications for test methods - Part 1-9: Electrical test
methods - Unbalance attenuation (transverse conversion loss TCL transverse conversion
transfer loss TCTL)
Kommunikationskabel - Spezifikationen für Prüfverfahren Teil 1-9: Elektrische
Prüfverfahren - Unsymmetriedämpfung (Unsymmetriedämpfung am nahen und am
fernen Ende)
Câbles de communication - Spécifications des méthodes d'essai Partie 1-9: Méthodes
d'essais électriques - Affaiblissement de disymétrie (perte de conversion longitudinale,
perte de transfert de conversion longitudinale)
Ta slovenski standard je istoveten z: prEN 50289-1-9:2016
ICS:
33.120.20 äLFHLQVLPHWULþQLNDEOL Wires and symmetrical
cables
oSIST prEN 50289-1-9:2016 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 50289-1-9:2016

---------------------- Page: 2 ----------------------
oSIST prEN 50289-1-9:2016

EUROPEAN STANDARD DRAFT
prEN 50289-1-9
NORME EUROPÉENNE

EUROPÄISCHE NORM

August 2016
ICS 33.120.20 Will supersede EN 50289-1-9:2001
English Version
Communication cables - Specifications for test methods - Part 1-
9: Electrical test methods - Unbalance attenuation (transverse
conversion loss TCL transverse conversion transfer loss TCTL)
Câbles de communication - Spécifications des méthodes Kommunikationskabel - Spezifikationen für Prüfverfahren
d'essai Partie 1-9: Méthodes d'essais électriques - Teil 1-9: Elektrische Prüfverfahren - Unsymmetriedämpfung
Affaiblissement de disymétrie (perte de conversion (Unsymmetriedämpfung am nahen und am fernen Ende)
longitudinale, perte de transfert de conversion longitudinale)
This draft European Standard is submitted to CENELEC members for enquiry.
Deadline for CENELEC: 2016-11-04.

It has been drawn up by CLC/TC 46X.

If this draft becomes a European Standard, CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CENELEC in three official versions (English, French, German).
A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to
the CEN-CENELEC Management Centre has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.



European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2016 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Project: 61098 Ref. No. prEN 50289-1-9:2016 E

---------------------- Page: 3 ----------------------
oSIST prEN 50289-1-9:2016
prEN 50289-1-9:2016
1 Contents Page
2 European foreword . 3
3 1 Scope . 5
4 2 Normative references . 5
5 3 Terms and definitions . 5
6 4 Test method . 6
7 4.1 Method A: measurement using balun setup . 6
8 4.1.1 Test equipment . 6
9 4.1.2 Test sample . 6
10 4.1.3 Calibration procedure . 7
11 4.1.4 Measuring procedure . 9
12 4.1.5 Expression of test results . 10
13 4.2 Method B: measurement using balun-less setup. 11
14 4.2.1 Test equipment . 11
15 4.2.2 Test sample . 12
16 4.2.3 Calibration procedure . 12
17 4.2.4 Measuring procedure . 12
18 4.2.5 Expression of test results . 13
19 5 Test report . 14
20 Annex A (informative) General background of unbalance attenuation . 15
21 A.1 General. 15
22 A.2 Unbalance attenuation near end and far end . 15
23 A.3 Theoretical background . 17
24 Bibliography . 21
25
2

---------------------- Page: 4 ----------------------
oSIST prEN 50289-1-9:2016
prEN 50289-1-9:2016
26 European foreword
27 This document [prEN 50289-1-9:2016] has been prepared by CLC/TC 46X "Communication cables".
28 This document is currently submitted to the Enquiry.
29 The following dates are proposed:
(doa) dor + 6 months
• latest date by which the existence of this document has to
be announced at national level
(dop) dor + 12 months
• latest date by which this document has to be implemented
at national level by publication of an identical national
standard or by endorsement
(dow) dor + 36 months
• latest date by which the national standards conflicting with
(to be confirmed or
this document have to be withdrawn
modified when voting)
30 This document will supersede EN 50289-1-9:2001.
31 EN 50289-1, Communication cables — Specifications for test methods, is currently composed with the
32 following parts:
33 — Part 1-1: Electrical test methods — General requirements;
34 — Part 1-2: Electrical test methods — DC resistance;
35 — Part 1-3: Electrical test methods — Dielectric strength;
36 — Part 1-4: Electrical test methods — Insulation resistance;
37 — Part 1-5: Electrical test methods — Capacitance;
38 — Part 1-6: Electrical test methods — Electromagnetic performance;
39 — Part 1-7: Electrical test methods — Velocity of propagation;
40 — Part 1-8: Electrical test methods — Attenuation;
41 — Part 1-9: Electrical test methods — Unbalance attenuation (transverse conversion loss TCL transverse
42 conversion transfer loss TCTL);
43 — Part 1-10: Electrical test methods — Crosstalk;
44 — Part 1-11: Electrical test methods — Characteristic impedance, input impedance, return loss;
45 — Part 1-12: Electrical test methods — Inductance;
46 — Part 1-13: Electrical test methods — Coupling attenuation or screening attenuation of patch cords /
47 coaxial cable assemblies / pre-connectorised cables;
48 — Part 1-14: Electrical test methods — Coupling attenuation or screening attenuation of connecting
49 hardware;
3

---------------------- Page: 5 ----------------------
oSIST prEN 50289-1-9:2016
prEN 50289-1-9:2016
50 — Part 1-15: Electromagnetic performance — Coupling attenuation of links and channels (Laboratory
51 conditions);
52 — Part 1-16: Electromagnetic performance — Coupling attenuation of cable assemblies (Field conditions);
53 — Part 1-17: Electrical test methods — Exogenous Crosstalk ExNEXT and ExFEXT.
4

---------------------- Page: 6 ----------------------
oSIST prEN 50289-1-9:2016
prEN 50289-1-9:2016
54 1 Scope
55 This draft European Standard details the test methods to determine the attenuation of converted differential-
56 mode signals into common-mode signals, and vice versa, due to balance characteristics of cables used in
57 analogue and digital communication systems by using the transmission measurement method. The
58 unbalance attenuation is measured in, respectively converted to, standard operational conditions. If not
59 otherwise specified, e.g. by product specifications, the standard operational conditions are a differential-mode
60 which is matched with its nominal characteristic impedance (e.g. 100 Ω) and a common-mode which is
61 loaded with 50 Ω. The difference between the (image) unbalance attenuation (matched conditions in the
62 differential and common-mode) to the Betriebs- (operational) unbalance attenuation (matched conditions in
63 differential-mode and 50 Ω reference load in the common-mode) is small provided the common-mode
64 impedance Z is in the range of 25 Ω to 75 Ω.
com
65 For cables having a nominal impedance of 100 Ω, the value of the common-mode impedance Z is about
com
66 75 Ω for up to 25 pair- count unscreened pair cables, 50 Ω for common screened pair cables and more than
67 25 pair- count unscreened pair cables, and 25 Ω for individually screened pair cables. The impedance of the
68 common-mode circuit Z can be measured more precisely either with a time domain reflectometer (TDR)
com
69 or a network analyser. The two conductors of the pair are connected together at both ends and the
70 impedance is measured between these conductors and the return path.
71 This draft European Standard is bound to be read in conjunction with prEN 50289-1-1, which contains
72 essential provisions for its application.
73 2 Normative references
74 The following documents, in whole or in part, are normatively referenced in this document and are
75 indispensable for its application. For dated references, only the edition cited applies. For undated references,
76 the latest edition of the referenced document (including any amendments) applies.
77 prEN 50289-1-1:2016, Communication cables — Specifications for test methods — Part 1-1: Electrical test
78 methods — General requirements
79 EN 50289-1-8, Communication cables — Specifications for test methods — Part 1-8: Electrical test
80 methods — Attenuation
81 EN 50290-1-2, Communication cables — Part 1-2: Definitions
82 3 Terms and definitions
83 For the purposes of this document, the terms and definitions given in EN 50290-1-2 and the following apply.
84 3.1
85 unbalance attenuation
86 logarithmic ratio of the differential-mode power (transmission signal of a balanced pair) to the common-mode
87 power (signal in the pair to ground/earth unbalanced circuit) measured at the near and at the far end
88 Note 1 to entry: The (operational) unbalance attenuation is described by the logarithmic ratio of the differential-mode
89 power to the common-mode power in standard operational conditions. If not otherwise specified, e.g. by product
90 specifications, the standard operational conditions are a differential-mode which is matched with its nominal
91 characteristic impedance (e.g. 100 Ω) and a common-mode which is loaded with 50 Ω:
5

---------------------- Page: 7 ----------------------
oSIST prEN 50289-1-9:2016
prEN 50289-1-9:2016
 
P U Z
diff diff com
 
92 a = 10×lg = 20×lg +10×lg (1)
u
 
P U Z
com com  diff 
93 where
P is the power in the differential-mode (balanced) circuit;
diff
P is the power in the common-mode (unbalanced) circuit;
com
U is the voltage in the differential-mode (balanced) circuit;
diff
U is the voltage in the common-mode (unbalanced) circuit;
com
Z is the characteristic impedance of the differential-mode (balanced) circuit;
diff
Z is the characteristic impedance of the common-mode (unbalanced) circuit.
com
94 3.2
95 transverse conversion loss
96 TCL
97 logarithmic ratio of the differential-mode injected signal at the near end to the resultant common-mode signal
98 at the near end of a balanced pair, and which is equal to unbalance attenuation at near end when the CUT is
99 terminated with the same impedances as defined for unbalance attenuation measurement
100 Note 1 to entry: This definition stems from ITU-G.117.
101 3.3
102 transverse conversion transfer loss
103 TCTL
104 logarithmic ratio of the differential-mode injected signal at the near end to the resultant common-mode signal
105 at the far end of a balanced pair, and which is equal to unbalance attenuation at far end when the CUT is
106 terminated with the same impedances as defined for unbalance attenuation measurement
107 Note 1 to entry: This definition stems from ITU-G.117.
108 4 Test method
109 4.1 Method A: measurement using balun setup
110 4.1.1 Test equipment
111 a) It is mandatory to create a defined return (common-mode) path. This is achieved by grounding all other
112 pairs and screen(s) if present in common to the balun ground. However in addition in the case of
113 unscreened cables the cable under test shall be wound onto a grounded metal drum. The drum surface
114 may have a suitable groove, wide enough to contain the cable, and shall be adequate to hold 100 m of
115 cable in one layer. The pair under test shall be terminated with differential-mode and common-mode
116 terminations and grounded at near and far ends
117 b) A network analyser or generator/receiver combination suitable for the required frequency and dynamic
118 range.
119 c) The baluns shall have a common-mode port and the characteristics given in prEN 50289-1-1:2016,
120 Table 1.
121 d) Time domain reflectometer (optional).
122 4.1.2 Test sample
123 The ends of the cable under test (CUT) shall be prepared so that the twisting of the pairs/quads is maintained
124 up to the terminals of the test equipment. If not otherwise specified the CUT shall have a length of
125 100 m ± 1 m. For the measurement or evaluation of the equal level unbalance attenuation at the far end the
126 following applies: if the CUT length is not otherwise specified and the attenuation of the CUT at the highest
127 frequency to be measured is higher than or equal to 80 dB the length of the CUT may be reduced to limit the
128 attenuation to maximum 80 dB.
6

---------------------- Page: 8 ----------------------
oSIST prEN 50289-1-9:2016
prEN 50289-1-9:2016
129 All pairs not under test and all screens shall be connected in common to the same ground as the balun at
130 both ends of the CUT.
131 For unscreened cables the CUT shall be wound tightly around the metal drum in one layer. The distance
132 between the windings should be at least the diameter of the cable. The metal drum shall be connected to the
133 same ground as the balun, e.g. by fixing the baluns to the drum.
134 4.1.3 Calibration procedure
135 a) The reference line calibration (0 dB-line) shall be determined by connecting coaxial cables between the
136 analyser input and output. The same coaxial cables shall also be used for the balun loss and unbalance
137 attenuation measurements. The calibration shall be established over the whole frequency range specified
138 in the relevant cable specification. This calibration method is valid for closely matched baluns that satisfy
139 the characteristics of Table 1.
140 b) Figure 1 gives the schematic for the measurement of the differential-mode loss of the baluns. Two baluns
141 are connected back to back on the symmetrical output side and their attenuation measured over the
142 specified frequency range. The connection between the two baluns shall be made with negligible loss.

U U U
0 diff 1
50 Ω
50 Ω
IEC  654/07
143
144 Key
145 U voltage at network analyser port or signal generator
0
146 U voltage at network analyser port or receiver
1
147 U voltage at symmetrical port of baluns
diff
148 Figure 1 — Test set-up for the measurement of the differential-mode loss of the baluns
149 The differential-mode loss of the baluns is given by:
 
U
0
 
( )
α = 0,5× 20×lg =−0,5× 20×lg S (2)
diff 21
 
U
1
 
150 where:
is the differential-mode loss of the balun (dB);
α
diff
S is the scattering parameter S (forward transmission coefficient) where port 1 is the primary
21 21
(unbalanced side) side of the near end balun and port 2 is the primary side (unbalanced port) of
the far end balun.
151 c) Figure 2 gives the schematic for the measurement of the common-mode loss of the baluns. The baluns
152 used in b) are connected together; the unbalanced balun ports are terminated with the nominal test
153 equipment impedance, the test equipment is connected to the common-mode port (centre tap) of the
154 baluns.
155
7

---------------------- Page: 9 ----------------------
oSIST prEN 50289-1-9:2016
prEN 50289-1-9:2016

U U
0
1
50 Ω 50 Ω
50 Ω
50 Ω
IEC  655/07
156
157 Key
158 U voltage at network analyser port or signal generator
0
159 U voltage at network analyser port or receiver
1
160 Figure 2 — Test set-up for the measurement of the common-mode loss of the baluns
161 The common-mode loss of the baluns is given by
 
U
0
 
α = 0,5× 20×lg =−0,5×(20×lg S )
(3)
com 21
 
U
1
 
162 where:
α is the common-mode loss of the balun (dB);
com
S is the scattering parameter S (forward transmission coefficient) where port 1 is the common-
21 21
mode port of the near end balun and port 2 is the common-mode port of the far end balun.
163 d) The operational attenuation of the balun α takes into account the common-mode and differential-
balun
164 mode losses of the balun:
α =α +α
(1)
balun diff com
165 where
166 α is the operational attenuation or intrinsic loss of the balun (dB).
balun
167 NOTE More precise results can be obtained using either poling of the baluns for α and α and averaging the results or using
diff com
168 three baluns. In the latter case, the assumption of identical baluns is not required.
169 e) The voltage ratio of the balun can be expressed by the turns ratio of the balun and the operational
170 attenuation of the balun:
U Z
diff diff
20×lg = 10×lg −α
balun
U Z
0 0

(4)
U Z
diff diff
20×lg = 10×lg −α
balun
U Z
1 1
171 where
172 U is the differential-mode voltage at the input of the cable under test (V);
diff
173 U is the voltage at the network analyser port or signal generator (V);
0
174 Z is the characteristic impedance of the differential-mode circuit (Ω);
diff
175 Z is the output impedance of the network analyser or signal generator (Ω);
0
176 U is the voltage at the input of the load (V);
1
177 Z is the input impedance of the load (Ω).
1
8

---------------------- Page: 10 ----------------------
oSIST prEN 50289-1-9:2016
prEN 50289-1-9:2016
178 4.1.4 Measuring procedure
179 All pairs/quads of the cable shall be measured at both ends of the CUT. The unbalance attenuation shall be
180 measured over the whole-specified frequency range and at the same frequency points as for the calibration
181 procedure.
182 The measurement is done under standard operational conditions, i.e. one is measuring the Betriebs-
183 (operational) unbalance attenuation. If not otherwise specified, e.g. by product specifications, the standard
184 operational conditions are a differential-mode which is matched with its nominal characteristic impedance
185 (e.g. 100 Ω) and a common-mode which is loaded with 50 Ω.
186 Figure 3 gives a schematic of the measurement for unbalance attenuation at the near end.

CUT
U
U diff 50 Ω
0
50 Ω
50 Ω
U
n, com
50 Ω
IEC  656/07
187
188 Figure 3 — Test set-up for unbalance attenuation at near end (TCL)
U
0
α = 20×lg =−20×lg S
(5)
meas 21
U
n, com
189 where
is the measured attenuation (dB);
α
meas
S is the scattering parameter S (forward transmission coefficient) where port 1 is the primary
21 21
(unbalanced) side of the near end balun and port 2 is the common-mode port of the near end
balun
U voltage in the primary (unbalanced) circuit at the near end balun
0
U voltage in the common-mode circuit (V) at the near end balun
n,com
190 Figure 4 gives a schematic of the measurement for unbalance attenuation at far end.
9

---------------------- Page: 11 ----------------------
oSIST prEN 50289-1-9:2016
prEN 50289-1-9:2016

CUT
U
U 50 Ω
0 diff
50 Ω
50 Ω
U
f, com
50 Ω
IEC  657/07
191
192 Figure 4 — Test set-up for unbalance attenuation at far end (TCTL)
U
0
α = 20×lg =−20×lg S
(7)
meas 21
U
f, com
193 where
is the measured attenuation (dB);
α
meas
S is the scattering parameter S (forward transmission coefficient) where port 1 is the primary
21 21
(unbalanced) side of the near end balun and port 2 is the common-mode port of the far end
balun;
U voltage in the primary (unbalanced) circuit at the near end balun;
0
U voltage in the common-mode circuit (V) at the far end balun.
n,com
194 4.1.5 Expression of test results
195 The unbalance attenuation is defined as the logarithmic ratio of the differential-mode power to the common-
196 mode power:
P
U Z
diff
diff com
α = 20×lg = 20×lg +10×lg
(8)
u,n
U Z
P
u, f diff
n,com
n,com
f,com
f,com

197 where
is the unbalance attenuation (dB) at the near end (subscript n) respectively far end (subscript
α
u
f);
P is the common-mode power (W) at the near end (subscript n) respectively far end (subscript
com
f);
P is the differential-mode power (W);
diff
Z is the nominal characteristic impedance of the differential-mode of the CUT;
diff
Z is the standardized operational impedance of the common-mode, 50 Ω.
com
198 When measuring with S-parameter test-sets, the output voltage of the generator is measured instead of the
199 differential-mode voltage in the cable under test. Taking the operational attenuation of the balun into account,
200 the formula for the unbalance attenuation near or far end is:
10

---------------------- Page: 12 ----------------------
oSIST prEN 50289-1-9:2016
prEN 50289-1-9:2016
P P
diff 0
α = 10×lg = 10×lg −α
u, n balun
P P
u, f n,com n,com
f, com f, com

(8)
U Z
0 com
= 20×lg +10×lg −α
balun
U Z
0
n, com
f, com
Z
com
α =α +10×lg −α
(9)
u, n meas balun
Z
f, n 0
201 The equal level unbalance attenuation at the far end is then:
Z
com
ELα =α +10×lg −α −α
(10)
u, f meas balun cable
Z
0
202 where
EL α is the equal level unbalance attenuation at far end (EL TCTL) (dB);
u,f
α is the unbalance attenuation (dB) at the near end (subscript n) respectively far end
u
(subscript f);
is the operational attenuation or intrinsic loss of the balun (dB);
α
balun
is the attenuation of the pair under test (dB) and is measured according to EN 50289-1-8;
α
cable
P is the common-mode power (W) at the near end (subscript n) respectively far end
com
(subscript f);
P is the differential-mode power (W);
diff
Z is the impedance of the generator (Ω);
0
Z is the standardized operational impedance of the common-mode, 50 Ω.
com
203 4.2 Method B: measurement using balun-less setup
204 4.2.1 Test equipment
205 Method B is the preferred one for balanced cables for frequencies above 1 000 MHz as it avoids the use of
206 baluns which are often limited to 1 000 MHz. With this configuration it is possible to change the operational
207 conditions for unbalance attenuation to any desired value of the differential-mode and common-mode
208 reference impedance.
209 It is mandatory to create a defined return (common-mode) path. This is achieved by grounding all other pairs
210 and screen(s) if present in common to the test system ground. However in addition in the case of unscreened
211 cables the cable under test shall be wound onto a grounded metal drum. The drum surface may have a
212 suitable groove, wide enough to contain the cable, and shall be adequate to hold 100 m of cable in one layer.
213 The pair under test shall be terminated with differential-mode and common-mode terminations and grounded
214 at near and far ends.
215 Multiport vector network analyser VNA (having at least 4 ports) with:
216 – S-parameter set-up;
217 – A mathematical conversion from unbalanced to balanced, i.e. the mixed mode set-up which is often
218 referred to as an unbalanced, modal decomposition or balun-less setup. This allows measurements of
219 balanced devices without use of an RF balun in the signal path. With such a test set-up, all balanced
220 and unbalanced parameters can be measured over the full frequency range;
11

---------------------- Page: 13 ----------------------
oSIST prEN 50289-1-9:2016
prEN 50289-1-9:2016
221 – Coaxial cables – where the characteristic impedance shall be the same as the nominal impedance of
222 the VNA – are needed to interconnect the network analyser, switching matrix and the test fixture. The
223 screen of the coaxial cables shall have a low transfer impedance, i.e. double screen or more with a
224 transfer impedance less than 100 mΩ/m at 100MHz. The screens of each cable shall be electrically
225 bonded to a common ground plane, with the screens of the cable bonded to each other at multiple
226 points along their length. To optimize the dynamic range, the total interconnecting cable attenuation
227 shall not exceed 3 dB at 1 000 MHz;
228 – To perform a calibration at the end of the coaxial interconnection cable coaxial reference standards,
229 so called calibration standards, i.e. a short circuit, an open circuit and a reference load, are required.
230 An alternative to the before mentioned open, short and load references is the use of an electronic
231 multiport calibration kit (E-cal module) which is supplied by the supplier of the VNA.
232 – If the calibration is performed at the test interface calibration reference artefact, i.e. a short circuit, an
233 open circuit and a reference load, are required. For further details refer to prEN 50289-1-1.
234 4.2.2 Test sample
235 The ends of the cable under test (CUT) shall be prepared so that the twisting of the pairs/quads is maintained
236 up to the terminals of the test equipment. If not otherwise specified the CUT shall have a length of
237 100 m ± 1 m. For the measurement or evaluation of the equal level unbalance attenuation at the far end the
238 following applies: if the CUT length is not otherwise specified and the attenuation of the CUT at the highest
239 frequency to be measured is higher than or equal to 80 dB the length of the CUT may be reduced to limit the
240 attenuation to maximum 80 dB.
241 All pairs not under test and all screens shall be connected in common to the test system ground at both ends
242 of the CUT.
243 For unscreened cables the CUT shall be wound tightly around the metal drum in one layer. The distance
244 between the windings should be at least the diameter of the cable. The metal drum shall be connected to the
245 test system ground.
246 4.2.3 Calibration procedure
247 It is not the intent of the standard to detail the algorithms applied by a VNA to correct the measured results
248 based on a calibration procedure but to detail the calibration procedure. Further information may be obtained
249 in the manuals of the VNA supplier.
250 A full 4-port single ended (SE) calibration shall be performed. The calibration shall be either performed at the
251 ends of the coaxial interconnection cables or on the test interface.
252 In the first case open, short and load measurements (using coaxial reference standards, so called calibration
253 standards) shall be taken at the ends of the coaxial interconnection cables of each port concerned, and
254 through and isolation measurements shall be taken on every pair combination of those ports. One may also
255 use an electronic multiport calibration kit (E-cal module) which reduces significantly the calibration time. As
256 the calibration plane is the end of the coaxial interconnection cables the ef
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.